产品目录

产品信息 »  产品目录  » 产业用通信元件/无线系统  » 其他 对应RS232C的元件

其他 对应RS232C的元件

温控器/变频型 HRSH090

    ・消耗功率减小53%。
     三变频实现了出色的节能效果!
    ・冷却能力:9.5kW(风冷)、11.0kW(水冷)
    ・温度稳定性:±0.1℃
    ・温度设定范围:5℃〜40℃

    ※提供样机试用服务
     请与最近的营业所联系

     营业所一览
系列设定温度
范围
冷却能力温度
稳定性
冷却方式循环液
HRSH0905~40℃9.5kW±0.1℃风冷冷冻式
水冷冷冻式
清水
脱离子水(纯水)
乙二醇水溶液(15%)

产品特点

■Power consumption reduced by 53%

Outstanding energy saving effect with the triple inverter!
The inverter respectively controls the number of motor rotations of the compressor, fan and pump depending on the load from the user’s equipment.

Power reducing effect of the inverter pump

Circulating fluid pressure adjustable

Discharge pressure of the circulating fluid can be set with the operation panel. The inverter pump automatically controls the discharge pressure to the set pressure without adjusting the bypass piping under various piping conditions. Power consumption can be reduced by this control.
(Operation to the set pump operating frequency is also possible.)

Variations

■Compact and lightweight 130 kg

Reduced-height double condenser structure

Simple operation

■Temperature stability ±0.1°C (when a load is stable)

By controlling the DC inverter compressor, DC inverter fan, and electronic expansion valve simultaneously, it maintains the good temperature stability when the heat load fluctuates.

■Electric conductivity control set (With DI filter + Solenoid valve kit for control)
■Circulating fluid can be heated without a heater.
■Power supply(24 VDC) available

Power can be supplied from the terminal block on the rear side to external switches etc.

■Globally compatible power supplies

Power supply applicable to 200 to 230 VAC, or 380 to 415 VAC
Transformers are unnecessary even when used overseas.

(Europe, Asia, Oceania, Central and South America)

■Shaped for easy supply of circulating fluid





■Easy cleaning of the tank
■Easy check of the circulating fluid level
■Tool-less inspection and cleaning of air-cooled condenser
■With unfixed caster
■Anchor bolt fixing bracket
■Convenient Functions
■Self Diagnosis and Check Display
■Communication Function
■Applications
■Global Supply Network
■SMC Thermo-chiller Variations

Go Top